5.3 Introduction to flat slabs
After this lesson you should be able to:
- Describe a flat slab system, slab supported directly on columns with or without drop panels and column heads, and say why it is chosen for offices, car parks and hospitals.
- Find the total static moment of a panel and split it into negative and positive moments and into column and middle strips by the direct design method of IS 456:2000 cl. 31.4 and cl. 31.5.5.
- Choose a flat slab thickness from cl. 31.2.1 and check punching shear at the critical perimeter of cl. 31.6, the check that most often governs flat slab design.
Theory
A flat slab is a reinforced concrete slab carried directly by columns, without beams. IS 456:2000 cl. 31.1 allows it to have drops (thickened slab panels around the columns) and flared column heads, and to be solid or ribbed on the soffit. Leaving out beams gives a flat soffit, simple formwork, lower storey heights and free routing of ducts and pipes, which is why flat slabs are common in offices, hospitals, car parks and warehouses. The price is that the slab must carry all the bending in both directions and must transfer the whole floor load into each column through a small area of concrete.
Load on a flat slab still has to travel to the columns, so the slab bends in both directions over the full panel, and the bending is concentrated along the lines joining the columns. IS 456 therefore divides each panel into design strips (cl. 31.1.1): a column strip on each column line, a quarter of the transverse span wide on each side of the line but not more than a quarter of the span being designed, and a middle strip between two column strips. The column strip carries the larger share of the moment, especially the negative moment over the columns.
Two analysis methods are permitted (cl. 31.3.1): the direct design method of cl. 31.4, a coefficient method for regular layouts, and the equivalent frame method of cl. 31.5, which models the slab and columns as frames in each direction. The direct design method can be used only when the layout is regular (cl. 31.4.1): at least three continuous spans each way, rectangular panels with long-to-short span ratio not more than 2.0, successive spans differing by not more than one-third of the longer span, column offsets within 10 per cent of the span, and design live load not more than three times the design dead load.
Near each column the slab must pass a large concentrated reaction through a small perimeter, and if the concrete is overstressed a cone of slab punches through around the column. This punching shear failure is sudden and has caused progressive collapses of car-park and building floors, so IS 456 checks it at a critical section d/2 from the column or drop face (cl. 31.6.1), with a limiting stress ks τc where τc = 0.25 √fck (cl. 31.6.3.1). Drop panels and column heads increase the depth or the perimeter exactly where punching is critical, which is why they are used on heavily loaded slabs.
Derivation
- Free body of a panel strip: take the strip of width l2 (transverse span) between two column lines, spanning ln (clear span face to face of columns). It carries W = wu l2 ln. Whatever the support moments, statics requires the midspan moment plus the average of the two support moments to equal the simple-span moment.
- Total static moment: for a uniformly loaded simple span, Mmax = (wu l2) ln²/8 = W ln/8. This is the cl. 31.4.2.2 value Mo = W ln/8, with ln not less than 0.65 l1 so that very large columns or capitals do not make the moment unrealistically small.
- Split for an interior span: a fixed-ended beam under uniform load has support moments w l²/12 and a midspan moment w l²/24, that is 2/3 and 1/3 of w l²/8. IS 456 cl. 31.4.3.2 uses 0.65 Mo negative and 0.35 Mo positive for interior spans, close to the fixed-end split and allowing for some column rotation.
- Across the width: the negative moment at an interior support goes 75 per cent to the column strip (cl. 31.5.5.1) and the positive moment 60 per cent to the column strip (cl. 31.5.5.3); the rest goes to the middle strip (cl. 31.5.5.4). Each strip is then designed as a wide beam, as for slabs in lessons 5.1 and 5.2.
- Punching shear: for a c1 × c2 column the critical perimeter at d/2 is b0 = 2 (c1 + d) + 2 (c2 + d) and the shear on it is Vu = wu [l1 l2 − (c1 + d)(c2 + d)]. The nominal stress τv = Vu/(b0 d) (cl. 31.6.2.1) must not exceed ks τc with ks = 0.5 + βc but not more than 1, βc being the short-to-long side ratio of the column, and τc = 0.25 √fck (cl. 31.6.3.1).
- Thickness: cl. 31.2.1 applies the span to effective depth ratios of cl. 23.2 to the longer span, multiplied by 0.9 when there are no drops conforming to cl. 31.2.2, with a minimum thickness of 125 mm.
Total static moment: Mo = W ln/8 with W = wu l2 ln and ln ≥ 0.65 l1 (kN m; wu in kN/m², lengths in m)Interior span: negative 0.65 Mo, positive 0.35 Mo (kN m)Column strip share: 75 per cent of interior negative, 60 per cent of positive; middle strip the rest (kN m)Column strip width: 0.25 l2 on each side of the column line, not more than 0.25 l1 (m)Punching: b0 = 2 (c1 + d) + 2 (c2 + d); τv = Vu/(b0 d) ≤ ks τc, ks = 0.5 + βc ≤ 1, τc = 0.25 √fck (mm, N/mm²)Thickness: l/d from cl. 23.2 on the longer span, × 0.9 without drops; minimum 125 mm (mm)Bar spacing: not more than 2 times the slab thickness (mm)
- The slab is supported on columns arranged on a regular rectangular grid and carries uniformly distributed gravity load.
- For the direct design method all the limits of cl. 31.4.1 are met; otherwise the equivalent frame method of cl. 31.5 is used.
- The column strip and middle strip moments are designed as wide beams with the Chapter 2 flexure formulas; partial safety factor 1.5 on loads.
- Punching shear is checked for the gravity reaction only; unbalanced moment transfer at edge and corner columns and lateral loads need further checks.
- Limits: this lesson covers interior panels in an introductory way; end-span coefficients, moments in columns (cl. 31.4.5), pattern loading (cl. 31.4.6), openings (cl. 31.8), shear reinforcement design and earthquake-resisting flat slab frames are outside it.
Codes and standards
Indian Standards are cited by number and clause only; no clause text, tables or figures are reproduced. Other standards are listed for comparison, not ranked.
- IS 456:2000 cl. 31.1 (flat slab with or without drops and column heads), cl. 31.1.1 (column strip 0.25 l2 each side but not more than 0.25 l1, middle strip, panel), cl. 31.2.1 (span to effective depth ratios of cl. 23.2 on the longer span, multiplied by 0.9 without drops, minimum thickness 125 mm), cl. 31.2.2 (drops rectangular, at least one-third of the panel length each way, half width at exterior panels), cl. 31.2.3 (column head within a 90 degree cone), cl. 31.3.1 (direct design or equivalent frame method).
- IS 456:2000 cl. 31.4.1 (direct design limits: three spans, ratio 2.0, offsets 10 per cent, successive spans within one-third, live load not more than three times dead load), cl. 31.4.2.2 (Mo = W ln/8, ln not less than 0.65 l1), cl. 31.4.3.2 (interior span 0.65 and 0.35), cl. 31.5.5.1, cl. 31.5.5.3 and cl. 31.5.5.4 (75 per cent and 60 per cent to the column strip, remainder to the middle strip), cl. 31.6.1 (critical section at d/2), cl. 31.6.2.1 (τv = V/(b0 d)), cl. 31.6.3.1 (ks = 0.5 + βc not more than 1, τc = 0.25 √fck), cl. 31.6.3.2 (shear reinforcement between τc and 1.5 τc, redesign above 1.5 τc), cl. 31.7.1 (bar spacing not more than 2 times the slab thickness); IS 1786 deformed bars.
- Indian, European and American practice are listed side by side and not ranked: the European concrete code (EN 1992-1-1) analyses flat slabs by equivalent frames, plastic or numerical methods and checks punching at a basic control perimeter some distance from the column with its own shear resistance expression and detailing; the American code (ACI 318) uses the direct design and equivalent frame methods for two-way slabs and checks two-way (punching) shear at a critical perimeter with its own stress limits. The values differ and are not reproduced here.
Worked examples
Problem. An interior panel of a flat slab floor is 6 m × 6 m between column centres, with 500 mm × 500 mm columns and no drops. The slab is 220 mm thick (average effective depth 190 mm), M25 concrete and Fe 415 bars, finish 1.0 kN/m² and imposed load 4.0 kN/m². The layout meets cl. 31.4.1. Find the strip moments, the steel and check deflection.
- Loads: w = 0.22 × 25 + 1.0 + 4.0 = 10.5 kN/m², wu = 15.75 kN/m² (factored live 6.0 is well under three times factored dead 9.75). ln = 6.0 − 0.5 = 5.5 m, more than 0.65 × 6 = 3.9 m.
- W = 15.75 × 6 × 5.5 = 519.75 kN; Mo = 519.75 × 5.5/8 = 357.3 kN m. Negative 0.65 × 357.3 = 232.3 kN m; positive 0.35 × 357.3 = 125.1 kN m.
- Strips: column strip 0.25 × 6 = 1.5 m each side of the column line, so 3.0 m wide; middle strip 3.0 m. Mu,lim = 0.138 × 25 × 1 000 × 190² = 124.5 kN m/m.
- Column strip: negative 0.75 × 232.3 = 174.2 kN m, or 58.1 kN m/m → Ast = 921 mm²/m → 12 mm at 120 mm (942 mm²/m) top. Positive 0.60 × 125.1 = 75.0 kN m, or 25.0 kN m/m → 377 mm²/m → 10 mm at 200 mm (393 mm²/m) bottom.
- Middle strip: negative 58.1 kN m (19.4 kN m/m → 290 mm²/m) and positive 50.0 kN m (16.7 kN m/m → 249 mm²/m); the minimum 0.12 per cent × 1 000 × 220 = 264 mm²/m governs the bottom: 10 mm at 250 mm (314 mm²/m) top and bottom. All spacings are within 2 × 220 = 440 mm.
- Deflection (cl. 31.2.1, no drops): basic 26 × 0.9 = 23.4 on the 6 m span; with the column strip bottom steel fs = 0.58 × 415 × 377/393 = 231 N/mm² and pt = 0.21 per cent, the Fig. 4 factor is about 1.85 (textbook curve fit), so the allowable l/d is about 43 ≥ 6 000/190 = 31.6.
Answer. Mo 357.3 kN m; column strip 12 mm at 120 mm top and 10 mm at 200 mm bottom; middle strip 10 mm at 250 mm; deflection passes
Problem. For the slab of Example 1, check punching shear at an interior column (a) for the 500 mm × 500 mm column and (b) if the column is reduced to 400 mm × 400 mm.
- (a) Critical perimeter at d/2: b0 = 4 × (500 + 190) = 2 760 mm. Vu = 15.75 × (6 × 6 − 0.69²) = 559.5 kN.
- τv = 559 500/(2 760 × 190) = 1.07 N/mm². ks = 0.5 + 1.0 = 1.5, limited to 1.0; τc = 0.25 √25 = 1.25 N/mm²; ks τc = 1.25 N/mm² ≥ 1.07: no shear reinforcement needed.
- (b) b0 = 4 × (400 + 190) = 2 360 mm; Vu = 15.75 × (36 − 0.59²) = 561.5 kN; τv = 561 500/(2 360 × 190) = 1.25 N/mm² (1.252), just above 1.25 N/mm².
- Since τv lies between τc and 1.5 τc = 1.875 N/mm², cl. 31.6.3.2 permits shear reinforcement; the usual and more robust choices are a drop panel, a column head or a thicker slab, which increase d or b0 at the column.
Answer. (a) 1.07 ≤ 1.25 N/mm²: safe; (b) 1.252 > 1.25 N/mm²: add a drop panel or shear reinforcement
Problem. A basement car park has column lines at 6.0, 8.0 and 6.0 m in one direction and four bays of 7.0 m in the other. The slab with drops carries imposed load 5.0 kN/m² and dead load 0.25 × 25 + 1.5 = 7.75 kN/m². Check the cl. 31.4.1 limits, size the drops over an interior column between 8 m and 7 m spans, and comment on a proposal to change the spans to 5.0, 8.0 and 5.0 m.
- Three or more continuous spans each way: yes. Panel ratios 8/7 = 1.14 and 7/6 = 1.17, both not more than 2.0.
- Successive spans: 8.0 − 6.0 = 2.0 m ≤ 8.0/3 = 2.67 m, and the end spans are shorter, not longer, than the interior span. Live load 1.5 × 5.0 = 7.5 kN/m² ≤ 3 × 1.5 × 7.75 = 34.9 kN/m². The direct design method may be used.
- Drops (cl. 31.2.2): at least one-third of the panel length each way: 8.0/3 = 2.67 m and 7.0/3 = 2.33 m, so about 2.7 m × 2.4 m over the interior column; at exterior panels the drop width at right angles to the free edge, measured from the column centre-line, is half the interior value.
- Bar spacing is limited to 2 × 250 = 500 mm (cl. 31.7.1); the drops also give the extra depth for punching at the columns.
- With spans 5.0, 8.0 and 5.0 m the difference 3.0 m exceeds 8.0/3 = 2.67 m, so the direct design method is no longer permitted; the slab must be analysed by the equivalent frame method (cl. 31.5).
Answer. Direct design permitted; drops about 2.7 m × 2.4 m; with 5–8–5 m spans use the equivalent frame method
Step-by-step procedure
- Fix the column grid, decide on drops and column heads, and check whether the layout meets cl. 31.4.1 for the direct design method; if not, use the equivalent frame method.
- Choose the thickness from cl. 31.2.1 (longer span, × 0.9 without drops, at least 125 mm) and check punching at the critical columns early, because it often decides the thickness or the drop size.
- For each span and direction find W, ln and Mo = W ln/8, and split it into negative and positive moments.
- Distribute the moments to column and middle strips (75 and 60 per cent to the column strip for interior negative and positive moments) and design each strip as a wide slab section.
- Detail the bars within 2 times the slab thickness, with the minimum lengths of cl. 31.7.3, extra top steel over the columns, and integrity (bottom) bars passing through the columns.
- Check punching at every column (interior, edge and corner, with openings deducted) and deflection, and design the columns for the moments transferred from the slab.
Site notes
- Punching failures start at columns: check top steel cover and position over the columns before concreting, because top bars pushed down reduce d where it matters most.
- Never cut openings for services close to a column without the designer's approval; cl. 31.6.1.2 reduces the critical perimeter for openings near the column.
- Strike formwork and back-prop according to the designer's sequence; early loading of young concrete by stacked materials is a common cause of punching distress and excessive deflection.
- Drop panels need their own formwork boxes; confirm their plan size and depth against the drawing, not just the slab thickness.
- Bottom bars passing through the column cage hold the slab up if punching occurs; do not omit them to ease congestion.
- Using the centre-to-centre span instead of the clear span ln in Mo = W ln/8.
- Taking the column strip as half the panel width when the span in the design direction is shorter (the 0.25 l1 cap).
- Checking punching at the column face instead of at d/2, or forgetting to deduct the area inside the critical perimeter from the load.
- Applying the direct design method to irregular layouts that break the cl. 31.4.1 limits.
- Forgetting the 0.9 multiplier on span/depth ratios for flat slabs without drops.
For interior flat slab panels with M25 concrete, Fe 415 bars and office loads, a thickness of about span/28 to span/32 without drops is a common starting point, and punching at an interior column usually passes when the column side is at least about twice the slab thickness. Check edge and corner columns separately: their shorter perimeters and transferred moments make them more critical.
Summary
- A flat slab is carried directly by columns, with or without drops and column heads; it saves storey height and formwork but concentrates load at the columns.
- The direct design method (cl. 31.4) applies to regular layouts; it starts from Mo = W ln/8 and splits it 0.65 and 0.35 for interior spans.
- Column strips (a quarter of the transverse span on each side of the column line) carry 75 per cent of interior negative and 60 per cent of positive moment; middle strips carry the rest.
- Thickness follows cl. 23.2 on the longer span, multiplied by 0.9 without drops, with at least 125 mm; bars are spaced at not more than 2 times the slab thickness.
- Punching shear is checked at d/2 from the column with τv = Vu/(b0 d) ≤ ks τc, τc = 0.25 √fck; drops, heads or thicker slabs cure failing checks.
Practice questions
Tap a question to see the answer.
1A 7 m × 7 m interior panel has 450 mm square columns and wu = 14 kN/m². Find Mo.
ln = 6.55 m; W = 14 × 7 × 6.55 = 641.9 kN; Mo = 641.9 × 6.55/8 = 525.6 kN m.
2Find the column strip width for spans l1 = 5 m (design direction) and l2 = 8 m.
0.25 × 8 = 2 m each side, but not more than 0.25 × 5 = 1.25 m, so 2.5 m in total.
3What is ks for a 300 mm × 600 mm column?
βc = 0.5, so ks = 0.5 + 0.5 = 1.0.
4Find the limiting punching stress τc for M30 concrete.
0.25 √30 = 1.37 N/mm².
5What is the largest bar spacing in a 200 mm flat slab?
2 × 200 = 400 mm.
6Why are drop panels used?
They thicken the slab over the columns, increasing the effective depth for punching shear and negative moment, and let the rest of the slab be thinner.
References
Standard texts, listed in no order of merit. Our explanations, examples and diagrams are original; nothing is copied from these books.
- S. U. Pillai, D. Menon, Reinforced Concrete Design, Tata McGraw Hill (now McGraw Hill Education (India)), 3rd edition, 2009.
- P. C. Varghese, Limit State Design of Reinforced Concrete, Prentice Hall of India (PHI Learning), 2nd edition, 2008.
- J. K. Wight, J. G. MacGregor, Reinforced Concrete: Mechanics and Design, Pearson, 6th edition, 2012.
- R. Park, T. Paulay, Reinforced Concrete Structures, John Wiley and Sons, 1975.