7.3 Introduction to raft foundations
After this lesson you should be able to:
- Explain when a raft (mat) foundation is chosen instead of isolated or combined footings, and the main raft types.
- Find the soil pressures under a rigid raft from the resultant of the column loads and its eccentricities, and check them against the allowable bearing pressure.
- Check whether a raft can be treated as rigid, balance a design strip, and check punching at a heavily loaded column.
Theory
A raft is a single slab under the whole building, or a large part of it, carrying all the columns and walls. It is chosen when the soil is weak enough that isolated footings would cover more than about half of the plan area, when loads are heavy and close together, when the soil is variable and differential settlement must be reduced, or when a basement needs a floor that resists uplift from groundwater. A raft spreads the load over the largest possible area and bridges over local soft spots.
Rafts take several forms: a flat slab of uniform thickness; a slab thickened under the columns; a slab with beams along the column lines (beam and slab raft); and cellular or box rafts for very heavy loads. A raft placed deep enough that the weight of the soil removed balances much of the building load is called a compensated or floating foundation; it reduces the net pressure on the soil and so the settlement.
The simplest analysis, the conventional rigid method, assumes the raft is stiff enough that it moves as a rigid plate. The soil pressure is then planar, exactly like the stress in a short column under axial load and biaxial bending: q = Q/A ± Q ey y/Ix ± Q ex x/Iy, where Q is the total column load and ex, ey are the distances of its resultant from the centroid of the raft. The pressures at the corners are compared with the allowable bearing pressure, and the raft is then divided into strips along the column lines, each designed as a continuous beam.
A raft is not truly rigid. Beam-on-elastic-foundation theory gives a characteristic length 1/λ, with λ = (ks b / 4 Ec I) raised to the power 1/4, where ks is the modulus of subgrade reaction. Textbooks treat a strip as rigid when the column spacing is less than about 1.75/λ; beyond that, a flexible analysis (plate on springs or finite elements) is used. IS 2950 (Part 1) is the Indian code for the design of raft foundations, and IS 456 gives the strength rules for the slab, including punching around each column under cl. 31.6.
Derivation
- Resultant: Q = ΣPi; its coordinates are X = ΣPi xi / Q and Y = ΣPi yi / Q, measured from a corner.
- Eccentricities from the raft centroid: ex = X − Lx/2 and ey = Y − Ly/2. The moments about the centroidal axes are My = Q ex and Mx = Q ey.
- Second moments of the rectangular raft area: Iy = Ly Lx³/12 about the axis parallel to y, and Ix = Lx Ly³/12 about the axis parallel to x.
- Planar pressure at a point (x, y) measured from the centroid: q = Q/A + My x/Iy + Mx y/Ix, the same form as combined axial stress and bending in strength of materials.
- A design strip carries column loads ΣP but the rigid-method pressure under it, q avg × b × L, rarely equals ΣP, because shear passes between strips. A common correction takes the average of the two and scales the column loads up and the pressure down (or the reverse) to that average, so the strip is in vertical equilibrium before its moments are found.
- Rigidity: for a strip of width b, thickness t and modulus Ec, I = b t³/12 and λ = (ks b/(4 Ec I))^(1/4); the strip is treated as rigid if the column spacing is below 1.75/λ.
Total load and resultant: Q = ΣP; X = ΣP x/Q, Y = ΣP y/Q (kN, m)Eccentricity: ex = X − Lx/2, ey = Y − Ly/2 (m)Pressure: q = Q/A + Q ex x/Iy + Q ey y/Ix (kN/m²; x, y from the centroid in m; I in m⁴)Rectangle: Iy = Ly Lx³/12, Ix = Lx Ly³/12 (m⁴)Raft is preferred when the required footing area exceeds about half the plan area (rule of thumb)Rigidity: λ = [ks b/(4 Ec I)]^(1/4) (1/m); rigid if spacing < 1.75/λ; Ec = 5 000 √fck (N/mm², cl. 6.2.3.1)Punching at an interior column: b0 = 4 (c + d); τv = Vu/(b0 d) ≤ ks 0.25 √fck (N/mm²)
- The rigid method assumes a planar soil pressure; it is reasonable for stiff rafts with fairly uniform column loads and spacings, and it is the usual first design.
- Column loads in the examples are service loads that already include the raft self-weight shared to the columns, compared with an allowable net bearing pressure.
- Example 3 balances a strip by the averaging method; the moments of a balanced strip can then be found as for a continuous beam (structural analysis chapters).
- The modulus of subgrade reaction is not a soil constant; it depends on the size of the loaded area, and the value used is the geotechnical engineer’s estimate.
- Limits: flexible-plate and finite-element analysis, piled rafts, uplift under groundwater and the detailed provisions of IS 2950 (Part 1) are outside this introduction.
Codes and standards
Indian Standards are cited by number and clause only; no clause text, tables or figures are reproduced. Other standards are listed for comparison, not ranked.
- IS 2950 (Part 1) for the design of raft foundations and IS 1904 for foundations in soils (named by number only); IS 456:2000 cl. 34.1 (uniform settlement and safe bearing capacity), cl. 34.1.2 (edge thickness), cl. 34.5.1 and 34.5.2 (minimum steel as for slabs, and 360 mm² per metre each way on each face where the section is thicker than 1 m).
- IS 456:2000 cl. 31.6.1, 31.6.2.1 and 31.6.3.1 (punching around columns), cl. 6.2.3.1 (Ec = 5 000 √fck), cl. 26.4.2.2 (50 mm cover), cl. 36.4.1 (load factors); IS 1786 for deformed bars.
- Indian, European and American practice are listed side by side and not ranked: in Europe the raft slab is designed to EN 1992-1-1 with soil-structure interaction under EN 1997-1; in the United States ACI 318 gives the slab strength rules and the committee report ACI 336.2R describes rigid and flexible methods for mats. Coefficients and factors are not reproduced here.
Worked examples
Problem. A raft 13 m (x) × 11 m (y) carries nine columns on a grid at x = 0.5, 6.5 and 12.5 m and y = 0.5, 5.5 and 10.5 m from one corner. Service loads in kN (rows at y = 0.5, 5.5, 10.5; columns in x order): 900, 1 400, 900; 1 400, 2 400, 1 600; 1 000, 1 500, 1 100. Allowable net bearing pressure 100 kN/m². Find the corner pressures.
- Q = 12 200 kN. ΣP x = 81 100 kN m, so X = 6.648 m; ΣP y = 69 100 kN m, so Y = 5.664 m.
- ex = 6.648 − 6.5 = 0.148 m and ey = 5.664 − 5.5 = 0.164 m; My = 12 200 × 0.148 = 1 800 kN m and Mx = 12 200 × 0.164 = 2 000 kN m.
- A = 143 m²; Iy = 11 × 13³/12 = 2 013.9 m⁴; Ix = 13 × 11³/12 = 1 441.9 m⁴.
- q = 85.31 + 0.894 x + 1.387 y, with x and y from the centroid (± 6.5 m and ± 5.5 m at the corners).
- Corners: 85.31 − 5.81 − 7.63 = 71.9; 85.31 + 5.81 − 7.63 = 83.5; 85.31 − 5.81 + 7.63 = 87.1; and 85.31 + 5.81 + 7.63 = 98.8 kN/m².
Answer. Pressures from 71.9 to 98.8 kN/m², all positive and within 100 kN/m²
Problem. A building 20 m × 30 m in plan has a total service load of 48 000 kN; the allowable bearing pressure is 120 kN/m². (a) Would isolated footings be sensible? (b) A 0.9 m thick M25 raft is proposed, with columns at 6 m and ks = 20 000 kN/m³. Check a 5 m wide strip for rigidity.
- (a) Area of footings needed = 1.1 × 48 000/120 = 440 m², which is 440/600 = 73 per cent of the plan. Footings would almost touch, so a raft is chosen. Average raft pressure = 1.1 × 48 000/600 = 88 kN/m², within 120 kN/m².
- (b) Ec = 5 000 × √25 = 25 000 N/mm² = 25 × 10⁶ kN/m². I = 5 × 0.9³/12 = 0.304 m⁴.
- λ = [20 000 × 5/(4 × 25 × 10⁶ × 0.304)]^(1/4) = (0.003 29)^(1/4) = 0.240 per m, so 1.75/λ = 7.31 m.
- The column spacing of 6 m is less than 7.31 m, so the strip may be analysed by the rigid method.
Answer. (a) footings would cover 73 per cent of the plan: use a raft (88 kN/m² average); (b) 1.75/λ = 7.31 m > 6 m: rigid method acceptable
Problem. For the raft of Example 1, take the strip along the middle row of columns (y from 3.0 to 8.0 m, width 5 m), carrying 1 400, 2 400 and 1 600 kN. (a) Balance the strip by the averaging method. (b) Check punching at the 600 mm square column carrying 2 400 kN, for a 900 mm raft with d = 830 mm, M25, using the average factored pressure.
- (a) On the strip centre line (y = 5.5 m, which passes through the raft centroid in y) the rigid pressure runs from 85.31 − 5.81 = 79.5 to 85.31 + 5.81 = 91.1 kN/m², average 85.31 kN/m². Soil reaction = 85.31 × 5 × 13 = 5 545.5 kN, against column loads of 5 400 kN.
- Average = (5 400 + 5 545.5)/2 = 5 472.7 kN. Column loads are scaled by 5 472.7/5 400 = 1.013 5 to 1 418.9, 2 432.3 and 1 621.5 kN, and the average pressure is scaled to 5 472.7/(5 × 13) = 84.20 kN/m².
- (b) Factored: Pu = 1.5 × 2 400 = 3 600 kN; qu = 1.5 × 85.31 = 128.0 kN/m². Perimeter side 600 + 830 = 1 430 mm, b0 = 5 720 mm.
- Vu = 3 600 − 128.0 × 1.43² = 3 338.3 kN; τv = 3 338 300/(5 720 × 830) = 0.70 N/mm² against 1.0 × 0.25 × √25 = 1.25 N/mm²: safe without shear reinforcement.
Answer. (a) balanced strip: loads 1 418.9, 2 432.3, 1 621.5 kN on 84.20 kN/m²; (b) punching τv 0.70 ≤ 1.25 N/mm²
Step-by-step procedure
- Compare the total footing area needed with the plan area; above about half, or with variable soil or a basement, consider a raft.
- Fix the raft outline, often with small overhangs so that its centroid is close to the load resultant.
- Find Q, X, Y, ex, ey and the planar pressures at the corners and key points; keep them positive and within the allowable pressure.
- Check rigidity with 1.75/λ; if the raft is flexible, use a beam-on-springs or plate model instead.
- Choose the thickness for punching at the most heavily loaded and edge columns.
- Divide into strips along the column lines, balance each strip, find its moments as a continuous beam, and design top and bottom steel with at least the slab minimum.
Site notes
- Rafts are large pours: plan the concrete supply, pump positions and construction joints with the designer before the day.
- Thick rafts heat up as the cement hydrates; temperature control (cool mixes, insulation, monitoring) prevents cracking from the difference between core and surface.
- Keep the excavation dry and the formation undisturbed; a raft on softened soil settles more.
- Waterproofing and uplift protection for basements must be complete before the groundwater level is allowed to recover.
- Top mats of heavy rafts need strong chairs designed for the weight of bars and workers during the pour.
- Assuming a raft is rigid without checking the column spacing against 1.75/λ.
- Forgetting the eccentricity of the load resultant and reporting only Q/A.
- Designing a strip for its column loads without balancing the soil reaction.
- Ignoring punching at edge and corner columns, which have shorter perimeters.
- Treating the modulus of subgrade reaction as a fixed soil property.
If the column loads are fairly even and the raft outline is roughly centred on them, the corner pressures stay within about 15 per cent of Q/A: in Example 1 they range from 71.9 to 98.8 kN/m² about an average of 85.3 kN/m².
Summary
- A raft carries the whole building on one slab; it is used when footings would cover much of the plan, on variable soil, or for basements.
- The rigid method gives a planar pressure q = Q/A ± Q ex x/Iy ± Q ey y/Ix from the load resultant.
- A strip is treated as rigid when the column spacing is below about 1.75/λ.
- Strips are balanced before their moments are found; punching is checked at each column.
- IS 2950 (Part 1) governs raft design in India, with IS 456 for the slab strength.
Practice questions
Tap a question to see the answer.
1A raft 10 m × 10 m carries 8 000 kN with ex = 0.25 m and ey = 0. Find the maximum and minimum pressure.
Q/A = 80; Iy = 10⁴/12 = 833.3 m⁴; 8 000 × 0.25 × 5/833.3 = 12.0; so 92.0 and 68.0 kN/m².
2Footings for a building would need 280 m² on a 400 m² plan. Raft or footings?
280/400 = 70 per cent, more than about half: a raft is likely the better choice.
3Find Ix for a raft 12 m (x) by 8 m (y).
Ix = 12 × 8³/12 = 512 m⁴.
4A strip has columns totalling 4 000 kN and a rigid-method soil reaction of 4 200 kN. What is the balanced load?
(4 000 + 4 200)/2 = 4 100 kN.
5What is a compensated (floating) raft?
A raft placed deep enough that the weight of soil removed balances much of the building load, reducing the net pressure.
6If 1/λ = 4 m, up to what column spacing may the strip be taken as rigid?
1.75 × 4 = 7.0 m.
References
Standard texts, listed in no order of merit. Our explanations, examples and diagrams are original; nothing is copied from these books.
- S. U. Pillai, D. Menon, Reinforced Concrete Design, Tata McGraw Hill (now McGraw Hill Education (India)), 3rd edition, 2009.
- P. C. Varghese, Limit State Design of Reinforced Concrete, Prentice Hall of India (PHI Learning), 2nd edition, 2008.
- J. K. Wight, J. G. MacGregor, Reinforced Concrete: Mechanics and Design, Pearson, 6th edition, 2012.
- R. Park, T. Paulay, Reinforced Concrete Structures, John Wiley and Sons, 1975.