5.1 One-way slabs
After this lesson you should be able to:
- Recognise when a slab acts one way, because it is supported on two opposite edges or because its longer span exceeds twice the shorter one, and model it as a 1 m wide beam.
- Design a one-way slab for flexure and shear with IS 456:2000, choosing depth from the deflection rule of cl. 23.2.1 and bars within the minimum steel, maximum diameter and spacing rules of cl. 26.5.2 and cl. 26.3.3.
- Detail main and distribution bars, cantilever slabs and their anchorage, and check an existing slab for a new load.
Theory
A slab is a plate whose thickness is small compared with its span. When it is supported on two opposite edges only, or when the panel is long and narrow, almost all of the load travels across the short direction to the supports. The slab then bends like a beam in that one direction and is called a one-way slab. IS 456:2000 Annex D (D-1.11) says that when the longer span exceeds twice the shorter span the slab shall be designed as spanning one way; lesson 5.2 shows why: by that ratio a two-way slab carries nearly all its load in the short direction anyway.
Because the bending is the same at every point across the width, the designer takes a strip 1 m wide, spanning the short direction, and designs it as a rectangular beam with b = 1 000 mm (lessons 2.1 and 2.2). Loads are expressed per square metre and moments per metre width. Slabs are thin and lightly reinforced, so the neutral axis is shallow and the steel always yields; the flexure formulas of Chapter 2 apply directly, and the minimum steel and the deflection limit usually decide the design more than strength does.
The steel across the span is the main reinforcement. Steel in the other direction is distribution steel: it spreads concentrated loads, ties the slab together and controls shrinkage and temperature cracking. IS 456:2000 cl. 26.5.2.1 asks for at least 0.15 per cent of the gross section in each direction with mild steel, reducible to 0.12 per cent with high strength deformed bars or welded fabric, and cl. 26.5.2.2 limits bar diameter to one-eighth of the slab thickness. Cl. 26.3.3 (b) limits main bar spacing to 3d or 300 mm and distribution bar spacing to 5d or 300 mm (Amendment No. 1).
Slabs rarely need shear reinforcement: the shear stress Vu/(b d) over a 1 m strip is small and the concrete alone (Table 19, lesson 3.1) usually carries it. Depth is normally chosen from deflection (lesson 4.1): with basic span/effective depth ratios of 20 for simply supported and 26 for continuous slabs, multiplied by the Fig. 4 factor, which for lightly reinforced slabs is often 1.3 to 2.0. For short two-way slabs the notes to cl. 24.1 also give span to overall depth ratios, but one-way slabs are checked with cl. 23.2.1. Cantilever slabs such as sunshades and balconies use the basic ratio 7 and must have their top bars anchored well back into the support.
Derivation
- Strip model: a one-way slab of span l under a uniform load w per square metre is equivalent to a beam of width 1 m carrying w kN per metre; for simple support Mu = wu l²/8 and Vu = wu l/2 per metre width; for a cantilever Mu = wu l²/2 and Vu = wu l.
- Required steel: from lesson 2.2, Mu = 0.87 fy Ast d (1 − Ast fy/(b d fck)), so Ast = 0.5 (fck/fy)[1 − √(1 − 4.6 Mu/(fck b d²))] b d with b = 1 000 mm. The section is under-reinforced if Mu ≤ Mu,lim = 0.138 fck b d² for Fe 415.
- Bar spacing: for bars of area Aφ, the spacing s that gives Ast per metre is s = 1 000 Aφ/Ast; it must also satisfy s ≤ 3d and ≤ 300 mm for main bars (cl. 26.3.3 (b) (1)).
- Minimum steel (cl. 26.5.2.1): Ast,min = 0.0012 b D for high strength deformed bars (0.0015 b D for mild steel), in each direction, and the bar diameter φ ≤ D/8 (cl. 26.5.2.2).
- Deflection (cl. 23.2.1): l/d ≤ 20 kt (simply supported), 26 kt (continuous) or 7 kt (cantilever), with kt from Fig. 4 using fs = 0.58 fy Ast,req/Ast,prov. More main steel lowers fs and raises kt, so a slab can pass deflection either by depth or by extra steel.
- Shear: τv = Vu/(1 000 d) is compared with τc of Table 19 for the steel continuing past the section; if τv ≤ τc no shear steel is needed. (IS 456 also allows an enhancement factor for thin solid slabs, cl. 40.2.1.1, not used in this lesson.)
Simply supported: Mu = wu l²/8, Vu = wu l/2 (kN m and kN per metre width; wu in kN/m², l in m)Cantilever: Mu = wu l²/2, Vu = wu l (kN m and kN per metre width)Steel: Ast = 0.5 (fck/fy)[1 − √(1 − 4.6 Mu/(fck b d²))] b d with b = 1 000 mm (mm² per metre)Bar spacing: s = 1 000 Aφ/Ast ≤ 3d and ≤ 300 mm for main bars; ≤ 5d and ≤ 300 mm for distribution bars (mm)Minimum steel: 0.0012 b D (HYSD bars) or 0.0015 b D (mild steel) in each direction; φ ≤ D/8 (mm², mm)Deflection: l/d ≤ 20 kt, 26 kt or 7 kt with fs = 0.58 fy Ast,req/Ast,prov (dimensionless; fs in N/mm²)Shear: τv = Vu/(1 000 d) ≤ τc (N/mm²)
- The slab is supported along two opposite edges, or ly/lx > 2, so bending in the long direction is small and covered by distribution steel.
- Loads are uniformly distributed; concentrated loads, openings and line loads from walls need an effective width or a separate analysis.
- The effective span of a simply supported slab is the clear span plus the effective depth, or the centre-to-centre distance of supports, whichever is less (cl. 22.2 (a)); continuous slabs are analysed as continuous beams (cl. 24.2).
- Partial safety factors 1.5 on loads and the design strengths of Chapter 2 apply; the slab is under-reinforced.
- Limits: this lesson does not cover two-way action (lesson 5.2), flat slabs, ribbed or hollow block slabs, or slabs on grade; the Fig. 4 factors quoted are from a textbook curve fit and should be read from the figure when close to the limit.
Codes and standards
Indian Standards are cited by number and clause only; no clause text, tables or figures are reproduced. Other standards are listed for comparison, not ranked.
- IS 456:2000 Annex D, D-1.11 (ly/lx greater than 2: design as spanning one way), cl. 24.1 (provisions of cl. 23.2 for beams apply to slabs), cl. 24.2 (slabs continuous over supports designed as continuous beams), cl. 23.2.1 (basic span/effective depth ratios 7, 20 and 26 with Fig. 4 factor), cl. 26.5.2.1 (minimum steel 0.15 per cent of the total cross-section with mild steel, 0.12 per cent with high strength deformed bars or welded wire fabric), cl. 26.5.2.2 (bar diameter not more than one-eighth of the slab thickness).
- IS 456:2000 cl. 26.3.3 (b) (1) main bars not more than 3d or 300 mm apart, (2) distribution bars not more than 5d or 300 mm apart (Amendment No. 1 replaced 450 mm by 300 mm), cl. 40.2.1 and Table 19 (shear strength of concrete, as in lesson 3.1), cl. 26.2.1 (development length, as in lesson 3.2); IS 1786 deformed bars.
- Indian, European and American practice are listed side by side and not ranked: the European concrete code (EN 1992-1-1) designs one-way slabs as beams of unit width with its own minimum and secondary reinforcement and spacing rules and limiting span/depth expressions; the American code (ACI 318) gives minimum thickness tables for one-way slabs by support condition, shrinkage and temperature reinforcement ratios and maximum spacing rules. The numerical values differ and are not reproduced here.
Worked examples
Problem. Design a simply supported one-way floor slab of effective span 3.6 m, 150 mm thick with 20 mm clear cover, M20 concrete and Fe 415 bars. Floor finish 1.0 kN/m² and imposed load 3.0 kN/m² (unit weight of reinforced concrete 25 kN/m³).
- Loads: self-weight 0.15 × 25 = 3.75, total 3.75 + 1.0 + 3.0 = 7.75 kN/m²; wu = 1.5 × 7.75 = 11.625 kN/m². Mu = 11.625 × 3.6²/8 = 18.83 kN m/m; Vu = 11.625 × 3.6/2 = 20.93 kN/m.
- d = 150 − 20 − 5 = 125 mm; Mu,lim = 0.138 × 20 × 1 000 × 125² = 43.1 kN m/m, so singly reinforced. Ast = 451 mm²/m, so 10 mm bars at not more than 174 mm.
- Deflection with 10 mm at 170 mm (462 mm²/m): fs = 0.58 × 415 × 451/462 = 235.1 N/mm², pt = 0.37 per cent, factor about 1.40 (curve fit 1.405), allowable l/d = 28.1 < actual 3 600/125 = 28.8: fails.
- With 10 mm at 150 mm (524 mm²/m): fs = 207.5 N/mm², pt = 0.42 per cent, factor about 1.52, allowable l/d = 30.4 ≥ 28.8: passes. Moment of resistance 21.6 kN m/m ≥ 18.83.
- Distribution steel 0.12 per cent × 1 000 × 150 = 180 mm²/m: 8 mm at 275 mm (183 mm²/m), within 5d and 300 mm. Main spacing 150 mm ≤ 3d = 375 and 300 mm; bar diameter 10 ≤ 150/8 = 18.75 mm.
- Shear: τv = 20 930/(1 000 × 125) = 0.167 N/mm², below τc ≈ 0.44 N/mm² for 0.42 per cent steel in M20 (Table 19): no shear steel.
Answer. 150 mm slab: 10 mm bars at 150 mm (deflection governs, not strength); 8 mm at 275 mm distribution
Problem. A cantilever sunshade projects 1.2 m from a lintel. It is 120 mm thick at the root with 20 mm clear cover, M20 and Fe 415, finish 0.5 kN/m² and an imposed load of 1.5 kN/m² adopted by the designer. Design the main and distribution steel.
- w = 0.12 × 25 + 0.5 + 1.5 = 5.0 kN/m²; wu = 7.5 kN/m²; Mu = 7.5 × 1.2²/2 = 5.40 kN m/m at the root.
- With 8 mm top bars, d = 120 − 20 − 4 = 96 mm; Ast = 161 mm²/m; minimum 0.0012 × 1 000 × 120 = 144 mm²/m, so 161 governs.
- 8 mm at 300 mm (168 mm²/m) would satisfy the area but not the spacing limit 3d = 288 mm; use 8 mm at 250 mm (201 mm²/m), at the top.
- Deflection: basic 7; fs = 0.58 × 415 × 161/201 = 192.8 N/mm² and pt = 0.21 per cent give the maximum Fig. 4 factor of 2.0, so allowable l/d = 14 ≥ actual 1 200/96 = 12.5.
- Anchor the top bars into the lintel and beyond for at least Ld = 47 × 8 = 376 mm (lesson 3.2). Distribution: 144 mm²/m, 8 mm at 300 mm (168 mm²/m) ≤ 5d and ≤ 300 mm.
Answer. 8 mm at 250 mm top (main), 8 mm at 300 mm distribution, anchored at least 376 mm
Problem. An existing slab panel 3 m × 7 m rests on walls along its 7 m sides. It is 125 mm thick (d = 100 mm) with 8 mm Fe 415 bars at 200 mm across the short span and 8 mm at 300 mm the other way, M20. The owner wants to add a 1.0 kN/m² stone floor and use the room for an imposed load of 2.0 kN/m². Is it adequate?
- ly/lx = 7/3 = 2.33 > 2 and it rests on two opposite edges, so it acts one way.
- Detailing: main 251 mm²/m and distribution 168 mm²/m both exceed 0.0012 × 1 000 × 125 = 150 mm²/m; spacings 200 ≤ 3d = 300 mm and 300 mm ≤ 5d and ≤ 300 mm: acceptable.
- Capacity: xu = 0.87 × 415 × 251.3/(0.36 × 20 × 1 000) = 12.6 mm; Mr = 0.87 × 415 × 251.3 × (100 − 0.42 × 12.6) = 8.59 kN m/m; this allows wu = 8 × 8.59/3² = 7.64 kN/m².
- New loading: 0.125 × 25 + 1.0 + 2.0 = 6.125 kN/m², wu = 9.19 kN/m² > 7.64 kN/m²: the slab is overstressed by about 20 per cent; the span/depth ratio 30 also exceeds what the existing steel supports.
- Advise a lighter finish, reduced use, or strengthening (an additional bonded layer or an intermediate support) after a structural assessment, not just the new floor.
Answer. Not adequate: needs wu 9.19 kN/m² against a capacity of 7.64 kN/m²
Step-by-step procedure
- Classify the slab: supported on two opposite edges, or ly/lx > 2, means one-way (D-1.11).
- Fix the effective span and choose a trial depth from deflection: l/d about 20 to 28 for simply supported and 26 to 35 for continuous slabs with Fe 415, then check exactly.
- Compute loads per square metre (self-weight, finishes, imposed), factor them, and find Mu and Vu per metre width (continuous slabs as continuous beams).
- Find Ast per metre, choose bar diameter (≤ D/8) and spacing (≤ 3d and ≤ 300 mm); provide at least the minimum steel.
- Check deflection with the provided steel and shear with τc; adjust spacing or depth if either fails.
- Provide distribution steel (minimum steel, ≤ 5d and ≤ 300 mm), detail top steel over continuous supports and in cantilevers with full anchorage, and show both layers clearly on the drawing.
Site notes
- Main bars go in the outer layer (closest to the tension face) with distribution bars inside them; reversing the layers reduces d and the slab's strength.
- Use cover blocks at about 1 m centres and chairs for top steel; top bars trodden down by workers during concreting are the most common cause of cracked cantilevers.
- Check slab thickness at several points before concreting, especially on sloping roofs and at sunshade roots.
- Do not cut chases or core holes through slabs after casting without the designer's approval: they cut main bars.
- Keep props under cantilever sunshades until the supporting wall and beam above provide the counterweight assumed in design.
- Placing the main bars of a cantilever slab at the bottom; the tension is at the top.
- Using the 0.12 per cent minimum on the effective depth instead of the gross section b D.
- Choosing bar spacing only from the required area and forgetting the 3d and 300 mm limits.
- Designing a long, narrow panel supported on four sides as two-way, or a near-square panel supported on two sides as two-way.
- Ignoring deflection: in slabs it, not strength, usually sets the thickness.
For simply supported one-way slabs with Fe 415 bars and residential or office loads, the deflection check usually governs: an effective depth of about span/28 to span/30 works with a little extra steel, and continuous slabs can be about 30 per cent thinner (26/20 = 1.3). Slab steel commonly lands between the 0.12 per cent minimum and about 0.5 per cent.
Summary
- A one-way slab is supported on two opposite edges or has ly/lx > 2; it is designed as a 1 m wide beam spanning the short direction.
- Flexure uses the Chapter 2 formulas with b = 1 000 mm; slabs are lightly reinforced and under-reinforced, and shear steel is rarely needed.
- IS 456 asks for at least 0.12 per cent HYSD steel (0.15 per cent mild steel) of the gross section in each direction, bars no larger than D/8, main bars at no more than 3d or 300 mm and distribution bars at no more than 5d or 300 mm.
- Depth is chosen from deflection using the span/depth ratios of cl. 23.2.1 with the Fig. 4 factor; extra steel can rescue a marginal deflection check.
- Cantilever slabs carry top steel that must be anchored well into the support and protected from being trodden down.
Practice questions
Tap a question to see the answer.
1A panel 3 m × 7 m is supported on all four edges. One-way or two-way design?
ly/lx = 2.33 > 2: one-way (D-1.11).
2Find the minimum steel per metre in each direction for a 150 mm slab with Fe 415 bars, and with mild steel.
0.0012 × 1 000 × 150 = 180 mm²; 0.0015 × 1 000 × 150 = 225 mm².
3What is the largest bar diameter allowed in a 120 mm slab?
120/8 = 15 mm, so 12 mm bars in practice.
4Find Mu per metre for a simply supported slab with wu = 12 kN/m² over 3 m.
12 × 3²/8 = 13.5 kN m/m.
5At what spacing do 8 mm bars give 200 mm² per metre?
1 000 × 50.3/200 = 251 mm, so 250 mm.
6A slab has d = 110 mm. What is the maximum spacing of its distribution bars?
The smaller of 5 × 110 = 550 mm and 300 mm: 300 mm.
References
Standard texts, listed in no order of merit. Our explanations, examples and diagrams are original; nothing is copied from these books.
- S. U. Pillai, D. Menon, Reinforced Concrete Design, Tata McGraw Hill (now McGraw Hill Education (India)), 3rd edition, 2009.
- P. C. Varghese, Limit State Design of Reinforced Concrete, Prentice Hall of India (PHI Learning), 2nd edition, 2008.
- J. K. Wight, J. G. MacGregor, Reinforced Concrete: Mechanics and Design, Pearson, 6th edition, 2012.
- R. Park, T. Paulay, Reinforced Concrete Structures, John Wiley and Sons, 1975.