8.1 Roof trusses and purlins
After this lesson you should be able to:
- Identify the main parts of a pitched roof truss and the role of purlins, sag rods and bracing.
- Apply IS 800:2007 cl. 7.2.4 effective lengths to truss compression members, and cl. 8.9 to purlin design including deflection and biaxial bending.
- Estimate illustrative roof imposed loads from IS 875 (Part 2):1987 Table 2 / cl. 4.5 and check a purlin and a truss top-chord force in worked examples.
Theory
A roof truss is a triangulated frame that carries roof loads to the supports as axial forces in its members, with bending secondary when joints are not pinned. The top chord (rafter) follows the roof slope, the bottom chord ties the supports, and the web members (struts and ties) triangulate the panels. Purlins are the secondary beams that sit on the top chord (or on rafters) and carry the roof sheeting; they span from truss to truss. Sag rods may support long purlin spans about their weak axis. Bracing in the plane of the roof and in vertical planes keeps the trusses stable under wind and during erection.
Under gravity loads the top chord is usually in compression and the bottom chord in tension; wind suction can reverse some forces, so members and connections must be checked for possible reversal. IS 800:2007 cl. 7.2.4 sets the effective length of compression members in bolted, riveted or welded trusses and braced frames at 0.7 to 1.0 times the distance between centres of connections for buckling in the plane of the truss, depending on end restraint, and equal to the distance between centres of intersection for buckling out of the plane of the truss. Angle struts are designed to cl. 7.5.
Purlins are designed as beams. IS 800:2007 cl. 8.9 requires design as uncased beams to cl. 8.2.1 and 8.2.2, with bending-stress limits from lateral instability of the compression flange and with deflections within the cladding limits of cl. 5.6.1. Continuity over supports may be used when calculating moments. Bending about the two axes is found separately and checked against the biaxial rules of Section 9. Where sheeting adequately restrains the purlin, cl. 8.3.5 notes that the purlin need not normally be checked for the restraining forces demanded by rafters or trusses that carry mainly roof loads, provided bracing or stressed-skin action is present in the plane of the rafters.
Imposed (live) loads on roofs are taken from IS 875 (Part 2):1987. For flat, sloping or curved roofs with slopes up to 10°, Table 2 gives 1.5 kN/m² on plan when access is provided and 0.75 kN/m² when access is only for maintenance, together with corresponding minimum concentrated loads. For sloping roofs steeper than 10°, the imposed load on roof membrane sheets or purlins is 0.75 kN/m² less 0.02 kN/m² for every degree above 10°, subject to a stated minimum. Members that directly support the roof covering are also checked for an incidental concentrated load of 0.90 kN on 12.5 cm (cl. 4.5), unless reduced with approval when planks and ladders distribute the load. For slopes greater than 10°, members supporting the purlins (trusses, beams, girders) may be designed for two-thirds of the imposed load on the purlins (cl. 4.5.1). Dead load of sheeting, purlins and services is taken from the project data or from IS 875 (Part 1).
Analysis of a determinate pitched truss under nodal loads can use the method of joints or the method of sections. For teaching, loads on a purlin line are often lumped at the panel points. Real design also includes wind (IS 875 Part 3), possible snow or dust, connection eccentricity, and second-order effects in slender compression chords. Plastic analysis of trusses is outside this lesson; elastic member design with the effective lengths of cl. 7.2.4 is the path used here.
EN 1993-1-1 and AISC 360 also cover truss and purlin design under their own rules; they are named for comparison only and are not ranked against IS 800.
Derivation
- Purlin spacing s along the slope; truss spacing B (centre to centre). Load width on one purlin ≈ s (slope measure) for loads defined on the roof surface, or s / cos θ when converting plan UDL to sloping surface.
- UDL on a simply supported purlin of span B: w = (dead + imposed) × tributary width. Mid-span moment M = w B² / 8 if simply supported; less if continuity is taken as allowed by cl. 8.9.
- Deflection δ = 5 w B⁴ / (384 E I) for a simply supported uniform load; compare with the cladding limit from cl. 5.6.1 (project-specific; often span/150 to span/180 for accessible roofs — use the contract value, not a guessed number, in real work).
- IS 875 (Part 2) Table 2 sloping roof > 10°: q = 0.75 − 0.02(θ − 10) kN/m² on plan for sheets/purlins, with the code minimum applied.
- Cl. 4.5.1: for θ > 10°, imposed load on trusses supporting purlins may be taken as (2/3) of the purlin imposed load.
- Truss top-chord compression (illustrative fink/king panels): from method of joints; effective length KL from cl. 7.2.4; design strength Pd = Ae fcd as in Section 7.
- γm0 = 1.10 (Table 5); E = 2.0 × 10⁵ N/mm².
Purlin simply supported: M = w L²/8; V = w L/2; δ = 5 w L⁴/(384 E I)IS 875 (P2) sloping roof θ>10°: q = 0.75 − 0.02(θ−10) kN/m² (plan), subject to code minimumTruss imposed (θ>10°, cl. 4.5.1): q_truss = (2/3) q_purlinTruss compression: KL = 0.7L to 1.0L in-plane; KL = L out-of-plane (cl. 7.2.4)Pd = Ae fcd; fcd from cl. 7.1.2.1 with χ(λ); γm0 = 1.10
- Examples use given section properties (design data), not a named handbook section.
- Purlins in Example 1 are treated as simply supported and laterally supported by sheeting for the in-plane (major-axis) check; weak-axis / biaxial effects are shown separately with given moments.
- Truss joints are taken as pinned for force analysis; secondary moments are neglected in the examples.
- Wind, snow, temperature and erection loads are named but not combined in the numerical examples.
- Deflection limits are applied with an illustrative span/150 check for learning; the governing cladding limit on a real project is the one in the specification (cl. 5.6.1).
- Imposed roof loads are from IS 875 (Part 2):1987 as verified on the box; always confirm the current official edition before design.
Codes and standards
Indian Standards are cited by number and clause only; no clause text, tables or figures are reproduced. Other standards are listed for comparison, not ranked.
- IS 800:2007 cl. 5.6.1 (deflection), cl. 7.2.4 (truss compression effective lengths), cl. 7.5 (angle struts, named), cl. 8.2.1 and 8.2.2 (beam design paths used by cl. 8.9), cl. 8.3.5 (purlins restrained by sheeting), cl. 8.9 (purlins and sheeting rails), Section 9 (biaxial bending, named), Table 5 (γm0 = 1.10).
- IS 875 (Part 2):1987 cl. 4.1 and Table 2 (imposed loads on roofs), cl. 4.2–4.4 (concentrated maintenance load, rain, dust — named), cl. 4.5 and 4.5.1 (loads on supporting members; two-thirds rule for slopes > 10°).
- Background: N. Subramanian, Design of Steel Structures, Oxford University Press, 2008; S. K. Duggal, Limit State Design of Steel Structures, McGraw Hill Education (India), 3rd edition, 2019.
- EN 1993-1-1 and AISC 360 also cover trusses and purlins; named for comparison only, not ranked.
Worked examples
Problem. Roof slope θ = 18°. Purlins span B = 6.0 m between trusses and are spaced s = 1.40 m measured along the slope. Sheeting dead load including fixings = 0.15 kN/m² on the sloping surface (given). Access is for maintenance only. Using IS 875 (Part 2):1987 Table 2 for sloping roofs steeper than 10°, find the imposed load on the purlins, the design UDL on one purlin (dead + imposed, slope measure), and the mid-span moment if the purlin is simply supported. A laterally supported purlin has Z_e = 60 × 10³ mm³, Z_p = 68 × 10³ mm³, fy = 250 N/mm², γm0 = 1.10. Check Md = βb Z_p fy/γm0 with βb = 1.0 against the factored moment with γ = 1.5 on both dead and imposed (illustrative single factor for learning).
- Imposed on sheets/purlins (Table 2, θ = 18°): q = 0.75 − 0.02(18 − 10) = 0.75 − 0.16 = 0.59 kN/m² on plan.
- Convert plan imposed to sloping surface: q_slope = 0.59 × cos 18° = 0.59 × 0.9511 = 0.561 kN/m².
- Service load on sloping surface = 0.15 + 0.561 = 0.711 kN/m².
- UDL on purlin w = 0.711 × 1.40 = 0.995 kN/m.
- Factored w_u = 1.5 × 0.995 = 1.493 kN/m.
- M_u = w_u B²/8 = 1.493 × 6²/8 = 6.719 kN·m.
- Md = 1.0 × 68e3 × 250 / 1.10 / 1e6 = 15.455 kN·m ≥ 6.719 kN·m — OK for this major-axis check.
- Still required on a real design: deflection vs cl. 5.6.1, shear, biaxial effects from self-weight and wind (Section 9), and continuity if used (cl. 8.9).
Answer. q = 0.59 kN/m² plan; Mu = 6.719 kN·m; Md = 15.455 kN·m OK
Problem. For the service UDL w = 0.995 kN/m of Example 1 and I = 120 × 10⁴ mm⁴ (given), check the mid-span deflection of the 6 m simply supported purlin against an illustrative limit of span/150. E = 2.0 × 10⁵ N/mm².
- δ = 5 w L⁴ / (384 E I).
- w = 0.995 N/mm; L = 6000 mm; E = 2.0e5 N/mm²; I = 1.20e6 mm⁴.
- L⁴ = 6000⁴ = 1.296e15.
- δ = 5 × 0.995 × 1.296e15 / (384 × 2.0e5 × 1.20e6) = 6.4476e15 / 9.216e13 = 69.96 mm.
- Limit L/150 = 6000/150 = 40 mm. 69.96 > 40 — fails the illustrative limit.
- Increase I, reduce span or spacing, or use continuity over supports (cl. 8.9) so that the service deflection meets the cladding limit of cl. 5.6.1.
Answer. δ ≈ 70.0 mm > 40 mm (L/150) — not OK; stiffen or shorten
Problem. A symmetric pitched truss spans L = 12 m with rise h = 3 m (θ = arctan(0.5) = 26.565°). Trusses are spaced 6 m. Panel points divide each rafter into three equal slope lengths. Factored gravity load on the roof (dead + imposed on plan, already factored) is 1.20 kN/m² on plan. Using cl. 4.5.1, the imposed part on the truss has already been taken as two-thirds of the purlin imposed load inside that 1.20 kN/m² figure (given). Find the factored load per truss, the approximate force in the top chord next to the support by resolving at the support joint (taking the bottom-chord reaction as vertical L/2 each end and the rafter axial), and the out-of-plane effective length of a top-chord panel if purlins restrain it at each panel point. Then with Ae = 2 400 mm², fcd = 90 N/mm² (given from a prior Section 7 calculation with KL from cl. 7.2.4), check Pd.
- Plan load width per truss = 6.0 m; factored line load on plan = 1.20 × 6 = 7.20 kN/m.
- Total factored vertical load on one truss = 7.20 × 12 = 86.4 kN; each support reaction R = 43.2 kN.
- Rafter slope length = √(6² + 3²) = 6.708 m; cos θ = 6/6.708 = 0.8944; sin θ = 0.4472.
- At the support, vertical reaction balances the vertical component of top-chord force F_c sin θ (bottom chord horizontal): F_c = R / sin θ = 43.2 / 0.4472 = 96.60 kN (compression).
- Out-of-plane KL for a top-chord panel between purlins: panel slope length = 6.708/3 = 2.236 m; cl. 7.2.4 → KL = 2.236 m out of plane.
- Pd = Ae fcd = 2400 × 90 / 1000 = 216 kN ≥ 96.6 kN — OK for this illustrative check.
- In-plane KL would be 0.7 to 1.0 × distance between connection centres (cl. 7.2.4); use the higher demand of in-plane and out-of-plane when selecting fcd.
Answer. Fc ≈ 96.6 kN; KL_out = 2.236 m; Pd = 216 kN OK
Step-by-step procedure
- Collect dead load of sheeting, insulation, purlins and services; get imposed roof load from IS 875 (Part 2) Table 2 for the slope and access condition; add wind/snow as required by the project.
- Space purlins from sheeting capacity and from an economical span; design each purlin for moment, shear, deflection (cl. 5.6.1) and biaxial effects (cl. 8.9, Section 9).
- Place trusses at a spacing that suits purlin span and building grid; analyse the truss for the governing load combinations.
- Design compression members with KL from cl. 7.2.4 (and cl. 7.5 for angles); design tension members for yielding, rupture and block shear as in Chapter 3.
- Detail bracing in the roof plane and vertically; check erection stability and camber if spans are long (cl. 5.6.1).
- Document assumptions, load path and connection forces for fabrication drawings.
Site notes
- Store trusses vertically in racks, not flat in a stack that bends slender chords.
- Erect with temporary guys until permanent bracing and purlins are in; never leave a free-standing truss overnight without guys.
- Check camber and span before releasing the crane; verify base-plate bolts and seating.
- Fix purlins with the specified cleats/bolts; install sag rods before loading the sheeting.
- Walk the roof only on designed routes; loose sheets are a fall and wind hazard.
- Using plan-area load on a sloping purlin without the cos θ conversion (or the reverse), so the UDL is wrong.
- Taking KL = 0.5L for every truss strut because the joint “looks fixed”; cl. 7.2.4 gives 0.7L to 1.0L in-plane and L out-of-plane between intersections.
- Designing purlins for strength only and ignoring cladding deflection limits (cl. 5.6.1 / 8.9).
- Forgetting possible load reversal under wind suction in top-chord and web members.
- Omitting bracing and relying on unfinished sheeting for stability during erection.
- Mixing IS 875 plan loads with slope-measured spacings without a clear unit check.
Purlins: beam design + cladding deflection (IS 800 cl. 8.9). Truss struts: KL from cl. 7.2.4 (0.7–1.0 in-plane, L out-of-plane). Roof imposed: IS 875 (P2) Table 2; for θ>10°, trusses may take 2/3 of purlin imposed (cl. 4.5.1).
Summary
- Purlins are secondary beams under the sheeting; design them to IS 800:2007 cl. 8.9 with deflection limits from cl. 5.6.1 and biaxial checks from Section 9.
- Truss compression members use KL = 0.7L to 1.0L in-plane and KL = L out-of-plane between intersections (cl. 7.2.4).
- Roof imposed loads come from IS 875 (Part 2):1987 Table 2; for slopes > 10°, supporting trusses may take two-thirds of the purlin imposed load (cl. 4.5.1).
- Sheeting that restrains purlins interacts with bracing or stressed-skin action (cl. 8.3.5); erection bracing is still required until the roof is complete.
- Always confirm the current official editions of IS 800 and IS 875 before design; examples here are illustrative.
Practice questions
Tap a question to see the answer.
1A roof slopes at 20°. What imposed load on plan does IS 875 (Part 2) Table 2 give for sheets/purlins on a sloping roof steeper than 10°?
q = 0.75 − 0.02(20 − 10) = 0.55 kN/m² on plan.
2State the out-of-plane effective length of a truss compression member between intersections per IS 800:2007 cl. 7.2.4.
KL equal to the distance between centres of intersection.
3A simply supported purlin span is 5 m with service UDL 1.2 kN/m. Find the mid-span moment.
M = wL²/8 = 1.2 × 25/8 = 3.75 kN·m.
4For a 15° roof, may a truss be designed for two-thirds of the imposed load on the purlins? Cite the clause.
Yes. IS 875 (Part 2):1987 cl. 4.5.1 applies when the slope is greater than 10°.
5Why does cl. 8.9 point purlin design to both cl. 8.2.1 and 8.2.2?
Because a purlin may be laterally supported by sheeting (8.2.1 path) or need a lateral-torsional buckling check (8.2.2) when the compression flange is not adequately restrained.
6E = 2×10⁵ N/mm², I = 800×10⁴ mm⁴, w = 0.8 N/mm, L = 4000 mm. Find δ = 5wL⁴/(384EI).
L⁴=2.56e14; δ = 5×0.8×2.56e14/(384×2e5×8e6) = 1.024e15/6.144e14 = 1.667 mm.
References
Standard texts, listed in no order of merit. Our explanations, examples and diagrams are original; nothing is copied from these books.
- N. Subramanian, Design of Steel Structures, Oxford University Press, New Delhi, 1st edition, 2008.
- S. K. Duggal, Limit State Design of Steel Structures, McGraw Hill Education (India), 3rd edition, 2019.